Features
1. [HIGH ACCURACY] Adopt high accuracy temperature and humidity measurement unit, small in size, with long term stability.
2. [WIDE VOLTAGE] Using special analog circuit, wide range of use, and has DC 1030V wide voltage power supply.
3. [LCD DISPLAY] The temperature and humidity transmitter has an LCD display, which is beautiful and easy to read.
4. [EASY INSTALLATION] The sensor transmission can be wall mounted or rail mounted, with compact structure.
5. [PARAMETER SETTING] Parameters can be directly modified through software settings or buttons, easy to operate.
6. [GOOD PROTECTION] With wide temperature and humidity range, high dustproof protection level, has strong practicability.
Specification
Item Type: Temperature Humidity Transmitter
Product Size: Approx. 147 x 88 x 41mm / 5.8 x 3.5 x 1.6in
Weight: Approx. 178 g / 6.3 oz
Power Supply Wiring: Wide voltage 10~30V DC power input. For 0-10V output devices, only 24V can be used.
Product Description:
The transmitter is an industrial wall mounted enclosure with a high degree of protection. The circuit adopts industrial grade microprocessor chip and high accuracy temperature and humidity sensor to ensure excellent reliability, high accuracy and interchangeability of the product. Using standard industrial interface 0~10V analog signal output, it can be connected to on site digital display, PLC, inverter, industrial control host and other equipment, safe and reliable, beautiful appearance, easy installation.
Parameter:
Model RS-WS-V10-2D-LCD
DC Power Supply (Default) DC 10~30V
Maximum Power Consumption Current Output 1.2W
Voltage Output 1.2W
A Quasi Accuracy Humidity 2%RH (60%RH, 25)
Temperature 0.4 (25)
B Quasi Accuracy Humidity 3%RH(60%RH,25)
Temperature 0.5 (25)
Temperature Range -40~+120, default -40~+80
Humidity Range 0%RH-100%RH
Circuit Working Temperature -20~+60
Circuit Working Humidity 0%RH~95%RH (non condensing)
Probe Working Temperature -40~+120, default -40~+80
Probe Working Humidity 0%RH-100%RH
Long Term Stability Humidity 1%RH/y
Temperature 0.1/y
Response Time Humidity 8s(1m/s wind speed)
Temperature 25s(1m/s wind speed)
Output Signal Voltage Output 0~10V
Load Capacity Voltage Output Output Resistance 250
Current Output 600
Hole Size Approx. 70mm / 2.8in
Parameter Settings Software Settings or Buttons to Modify Directly
Specific Wiring:
Circuit Identification Description
Power Supply VCC Power Positive
GND Power Negative, Signal Negative
Output TH Temperature Signal Positive
RH Humidity Signal Positive
Common Problems and Solutions:
No Output or Output Errors, Possible Causes:
- The error corresponding to the range leads to the PLC calculation error. For the range, please refer to the technical indicators in the first part.
- The wiring method is incorrect or the wiring sequence is wrong.
- The power supply voltage is wrong (for the 0-10V type, the power supply is 24V).
- The distance between the transmitter and the collector is too long, causing signal disorder.
- The PLC acquisition port is damaged.
- The equipment is damaged.
Package List
2 x Screws
2 x Expansion Tubes
1 x Transmitter
1 x User Manual